Комментарии:
Mal trabajo
ОтветитьFirst
ОтветитьWrong placement of beam,
Inner beams should always lie on peripheral beams..
This will result in deflection and shear failure.
135 degree
ОтветитьQue es una viga comprimida..?? Hay más barras arriba que abajo...no levantan hierros para corte en apoyos??
ОтветитьExtra bar on top is wrong. It should be in bottom
ОтветитьLigatures hooks are not to standards, length, also does not meet seismic code 135 degree hooks, second raw of top bars away from tension axis should be raised a bit
ОтветитьPrimero los estribos deben de tener ganchos, en las vigas trabajan los hierros superiores e inferiores, se ponen hierros latersles en vigas qué tienen gran altura
ОтветитьC'e' quel ferro filante laterale che non arriva sulla trave, occorrono altri due ferri filanti ( 2+2) laterali e'normativa , la trave e' alta ⚠️
Ответить1) The angle at the ties are meant to be at 135 degrees for better shear resistance, not 90 as done.
2) If double reinforcement is required, it should be at the bottom not the top
Ring hook is not bent to 135⁰
Ответить